TSS Polymer Control for Centrifuges and DAF

Closed-loop polymer dosing for decanter centrifuges and DAF: the dose follows the solids load and is trimmed on measured centrate or underflow quality.

A fixed polymer setpoint assumes the feed never changes. The Archer TSS control block sets the polymer dose from measured process conditions instead: forward from the dry solids load arriving at the machine, and back from the quality of the centrate or DAF underflow leaving it.

TSS control block for a decanter centrifuge: feedforward on feed TSS times flow, feedback trim on centrate TSS, and the pump curve to polymer pump speed
The TSS control block: feedforward from the solids load, a bounded feedback trim on centrate TSS, and the dosing pump characteristic.

How the loop works

1. Feedforward

Feed flow and feed solids give the dry solids load. A commissioned characteristic converts that load into a base dose per dry tonne, so when the sludge thickens or the feed steps up, the dose moves with it in the same second.

2. Feedback trim

Dose against centrate TSS is a U-curve. A bounded trim raises or lowers the base dose within a commissioned band, and checks periodically which side of the curve it is on before it moves, so it holds the plant near the trough.

3. Pump output

The commanded dose is linearised through the dosing pump’s own characteristic into a speed reference, so the same dose is delivered across the pump’s range. The output is rate-limited to protect the floc and the pump.

4. Verify

The polymer flowmeter confirms the delivered rate, and the computed dose in kg active per tonne of dry solids goes to the HMI and the historian.

Built to fail safe

Every signal is checked for quality, range and staleness. When an input fails, the loop steps down rather than stopping, and every transition is time-stamped in the PLC alarm history.

  • Centrate TSS bad or stale: the trim is frozen at its last good value and feedforward continues
  • Feed solids or flow bad: recipe nominal or last good rate
  • Both feed signals lost: back to the last known good fixed rate
  • Dose at a clamp: alarm, the loop continues at the clamp
  • Machine not running or high scroll torque: standby or trim frozen
  • Manual override from the HMI at any time, with bumpless return to auto
Feed solids0 to 8 % DS, 4–20 mA or fieldbus
Feed flow0 to 60 m³/h, 4–20 mA, pulse or fieldbus
Centrate TSS0 to 3,000 mg/l, 4–20 mA or fieldbus
Polymer flow0 to 2,000 l/h, 4–20 mA or pulse
OutputPolymer pump speed, 4–20 mA or fieldbus, rate-limited and clamped
Execution500 ms in the machine PLC

Typical ranges; set to the installed instruments at commissioning.

Where it runs

In the centrifuge PLC

A TwinCAT 3 function block or a Rockwell Add-On Instruction with an HMI faceplate, from the Archer library.

In an Archer panel

A Beckhoff CX-series controller with analogue I/O, where the machine PLC cannot host the block.

On the IIoT Gateway

For DAF, the same block runs on the IIoT Gateway with influent and underflow TSS probes.

The block writes to the polymer dosing pump only. It does not change centrifuge protection, drive control or machine interlocks, and the remote monitoring link stays read-only. Source code and documentation are handed over, and the loop runs on plant hardware under plant control.

Commissioning

Baseline2 to 4 weeks: existing dose, feed variability and centrate quality recorded before any automation is enabled
Step tests1 to 2 days: dose stepped across its working range at steady feed to map the centrate response and find the trough
Closed-loop trial1 to 2 weeks: coefficients, pump curve, clamps and trim authority set from the test data; loop run in auto at reduced authority with the operators
Handover and reviewOperator training, loop folder and as-commissioned settings; dose per dry tonne and centrate quality reviewed against the baseline after the first quarter

Closed-loop performance depends on the accuracy and maintenance of the feed and centrate analysers. Specifications are typical and subject to change; final configuration is confirmed in Archer’s scope of supply.

Scope it for your machine

Tell us about the centrifuge or DAF, the polymer system and the instruments fitted, and we will tell you what closed-loop control would need on your site.

Download the TSS control datasheet (PDF) · Centrifuge questionnaire · DAF questionnaire