TSS Polymer Control for Centrifuges and DAF
Closed-loop polymer dosing for decanter centrifuges and DAF: the dose follows the solids load and is trimmed on measured centrate or underflow quality.
A fixed polymer setpoint assumes the feed never changes. The Archer TSS control block sets the polymer dose from measured process conditions instead: forward from the dry solids load arriving at the machine, and back from the quality of the centrate or DAF underflow leaving it.

How the loop works
1. Feedforward
Feed flow and feed solids give the dry solids load. A commissioned characteristic converts that load into a base dose per dry tonne, so when the sludge thickens or the feed steps up, the dose moves with it in the same second.
2. Feedback trim
Dose against centrate TSS is a U-curve. A bounded trim raises or lowers the base dose within a commissioned band, and checks periodically which side of the curve it is on before it moves, so it holds the plant near the trough.
3. Pump output
The commanded dose is linearised through the dosing pump’s own characteristic into a speed reference, so the same dose is delivered across the pump’s range. The output is rate-limited to protect the floc and the pump.
4. Verify
The polymer flowmeter confirms the delivered rate, and the computed dose in kg active per tonne of dry solids goes to the HMI and the historian.
Built to fail safe
Every signal is checked for quality, range and staleness. When an input fails, the loop steps down rather than stopping, and every transition is time-stamped in the PLC alarm history.
- Centrate TSS bad or stale: the trim is frozen at its last good value and feedforward continues
- Feed solids or flow bad: recipe nominal or last good rate
- Both feed signals lost: back to the last known good fixed rate
- Dose at a clamp: alarm, the loop continues at the clamp
- Machine not running or high scroll torque: standby or trim frozen
- Manual override from the HMI at any time, with bumpless return to auto
| Feed solids | 0 to 8 % DS, 4–20 mA or fieldbus |
|---|---|
| Feed flow | 0 to 60 m³/h, 4–20 mA, pulse or fieldbus |
| Centrate TSS | 0 to 3,000 mg/l, 4–20 mA or fieldbus |
| Polymer flow | 0 to 2,000 l/h, 4–20 mA or pulse |
| Output | Polymer pump speed, 4–20 mA or fieldbus, rate-limited and clamped |
| Execution | 500 ms in the machine PLC |
Typical ranges; set to the installed instruments at commissioning.
Where it runs
In the centrifuge PLC
A TwinCAT 3 function block or a Rockwell Add-On Instruction with an HMI faceplate, from the Archer library.
In an Archer panel
A Beckhoff CX-series controller with analogue I/O, where the machine PLC cannot host the block.
On the IIoT Gateway
For DAF, the same block runs on the IIoT Gateway with influent and underflow TSS probes.
The block writes to the polymer dosing pump only. It does not change centrifuge protection, drive control or machine interlocks, and the remote monitoring link stays read-only. Source code and documentation are handed over, and the loop runs on plant hardware under plant control.
Commissioning
| Baseline | 2 to 4 weeks: existing dose, feed variability and centrate quality recorded before any automation is enabled |
|---|---|
| Step tests | 1 to 2 days: dose stepped across its working range at steady feed to map the centrate response and find the trough |
| Closed-loop trial | 1 to 2 weeks: coefficients, pump curve, clamps and trim authority set from the test data; loop run in auto at reduced authority with the operators |
| Handover and review | Operator training, loop folder and as-commissioned settings; dose per dry tonne and centrate quality reviewed against the baseline after the first quarter |
Closed-loop performance depends on the accuracy and maintenance of the feed and centrate analysers. Specifications are typical and subject to change; final configuration is confirmed in Archer’s scope of supply.
Scope it for your machine
Tell us about the centrifuge or DAF, the polymer system and the instruments fitted, and we will tell you what closed-loop control would need on your site.
Download the TSS control datasheet (PDF) · Centrifuge questionnaire · DAF questionnaire
Related pages
- Remote Monitoring: the centrifuge monitoring service
- IIoT Gateway: DAF process and chemical dosing controller
- Polymer Systems: make-down and dosing
- Decanter Centrifuges
- Control Panels