A DAF process and chemical dosing controller: every chemical measured, controlled and verified from one 7-inch touchscreen.
The Archer IIoT Gateway is a purpose-built controller for dissolved air flotation and chemical treatment systems. It combines multi-pump chemical metering, closed-loop dosing, sensor and pump calibration and secure cloud connectivity in one panel-mount unit, and replaces open-loop dosing and manually tuned loops with measured, verified, self-tuning control.

Why a DAF needs one
Most DAF systems run open-loop. Polymer is overfed to be safe, pH loops hunt around neutral, and a dosing problem only shows when the effluent goes out of specification.
The Gateway closes every loop: it measures what is in the water, doses each chemical against it, and checks what was actually delivered with a flowmeter on every chemical line.
Measure, control, verify
Measure
pH, ORP, turbidity, TSS, conductivity and streaming current over Modbus RTU, Modbus TCP/IP, EtherNet/IP or 4–20 mA, with automated probe cleaning and guided calibration.
Control
Up to three self-tuning PID loops drive up to four metering pumps, with adaptive linearised pH control and TSS feedforward and feedback dosing.
Verify
A flowmeter on each chemical line compares the commanded dose with the delivered dose, in ppm, on screen at all times.
Report
An on-board historian logs every loop; secure MQTT streaming puts live values, trends and alarms on a cloud dashboard.
Control capabilities
Stable pH, one tune
Adaptive linearised pH control holds steady across the full titration curve, for acid and caustic neutralisation, without retuning when the feed chemistry changes.
Polymer dosed to the water
TSS-based polymer control: feedforward on the influent solids load with feedback trim on underflow TSS, using one or two TSS probes. See TSS polymer control.
Coagulant optimisation
Streaming current analyser support for charge-based coagulant dosing against an operator setpoint.
Tuning without a specialist
Built-in autotune characterises each loop and suggests parameters for the operator to review, so loops are commissioned in hours.
Calibration built in
Guided calibration for dosing pumps and every connected sensor, plus solenoid-driven air or water probe cleaning that reduces drift in fouling streams.
Safe in manual
AUTO, MAN, fixed-dose ppm and dose ON/OFF per pump, with bumpless transfer: an operator can take any pump from the screen at any time.

Specifications
| Controller | 64-bit quad-core ARM industrial compute module, 4 GB RAM (8 GB optional), industrial eMMC, hardened embedded Linux; fanless, no moving parts |
|---|---|
| Display | 7-inch industrial TFT, 1024 × 600, projected-capacitive touch usable with wet fingers and gloves; panel-mount faceplate |
| Pump channels | Up to 4 metering pumps: 4–20 mA speed reference or pulse output, run/enable relay, run and fault feedback per pump |
| Control loops | Up to 3 independent PID loops, direct or reverse acting, with autotune |
| Sensor interfaces | Modbus RTU (RS-485), Modbus TCP/IP, EtherNet/IP, isolated 4–20 mA / 0–10 V; mixed configurations supported |
| Inputs and outputs | Dry-contact status and pulse inputs; 4–20 mA and relay outputs; dedicated solenoid outputs for probe cleaning; remote I/O expansion over Modbus TCP |
| Communications | MQTT over TLS to the cloud dashboard; on-board historian with trend screens and data export |
| Power and environment | 24 VDC (18–30 VDC), about 15 W; 0 to 50 °C; IP65 front panel |
Preliminary. Specifications are typical and subject to change; final configuration is confirmed in Archer’s scope of supply.
Applications
Configure a Gateway for your plant
Tell us the DAF or dosing duty, the chemicals, the pumps and the instruments already fitted, and we will configure and quote a Gateway for it. Existing instruments can usually be reused.
Online questionnaire
Fill in the scoping questions online instead of on paper.
Related pages
- Remote Monitoring: centrifuge monitoring and the Archer IIoT platform
- TSS polymer control: closed-loop polymer dosing for centrifuges and DAF
- DAF / Dissolved Air Flotation Systems
- Chemical Systems: dosing skids for coagulant, polymer, acid and caustic
- JarLab: choose the chemistry from jar tests and plant data
- Control Panels